2 changes: 1 addition & 1 deletion docs/configuration/zones.md
Original file line number Diff line number Diff line change
Expand Up @@ -81,7 +81,7 @@ Cooling mode assumed:
* `hvac-device`: at this point, the economizer is an on/off device (multistage coming). This is the identifier of the [HVAC device](./hvac.md) acting as an economizer.
* `timeout`: treat both indoor and ambient sensors as stale and shut off the economizer after not receiving data from them for this long. Default is 90 seconds. The system will complain at `INFO` level if this is happening.
* `settings`: This section is optional. If missing, it is assumed that the [schedule](./schedule.md) will take care of configuring economizer settings dynamically.
* `changeover-delta`: ambient temperature has to be this much lower than indoors for the economizer to start working (subject to PID configuration).
* `changeover-delta`: ambient temperature has to be this much lower than indoors for the economizer to start working (subject to PID configuration). Surprisingly, a value of 0 works well due to [PID control magic](https://en.wikipedia.org/wiki/Proportional%E2%80%93integral%E2%80%93derivative_controller).
* `target-temperature`: shut the economizer off when indoor temperature drops to this value.
* `keep-hvac-on`: set to `true` if you want the main HVAC to be still working when the economizer is active (maximum comfort), and to `false` if you want to stop it (maximum cost savings).

Expand Down
5 changes: 4 additions & 1 deletion docs/release-notes.md
Original file line number Diff line number Diff line change
@@ -1,7 +1,10 @@
Home Climate Control: Release Notes
==

## Coming Up
## Coming Up: v4.3.0

* Bugfix: [#320 Economizer runs forever when there is an ambient sensor failure](https://github.com/home-climate-control/dz/issues/320)
* Breaking change: [economizer configuration syntax](../configuration/zones.md#economizer) changed to allow future enahancements

## v4.2.0 (2024-01-17)

Expand Down
2 changes: 1 addition & 1 deletion docs/release-notes/v4.1.0.md
Original file line number Diff line number Diff line change
Expand Up @@ -3,7 +3,7 @@ Home Climate Control: v4.1.0. Release Notes

Release focus: stability improvements.

Bugfixes and enhancements:
## Bugfixes and enhancements
* [#298 HCC now advertizes itself over mDNS](https://github.com/home-climate-control/dz/issues/298)
* [#296 MQTT devices relying on retained messages may not work correctly](https://github.com/home-climate-control/dz/issues/296)
* [#295 Multiple ESPHome logical devices per physical device will report "available" only for one random](https://github.com/home-climate-control/dz/issues/295)
Expand Down
2 changes: 1 addition & 1 deletion docs/release-notes/v4.2.0.md
Original file line number Diff line number Diff line change
Expand Up @@ -3,7 +3,7 @@ Home Climate Control: v4.2.0. Release Notes

Release focus: project structure.

Bugfixes and enhancements:
## Bugfixes and enhancements
* [#304 Simplified project layout](https://github.com/home-climate-control/dz/issues/304)
* [#303 Single invalid Zigbee2MQTT no longer causes a cascading failure](https://github.com/home-climate-control/dz/issues/303)
* [#300 Ported the raise() logic from imperative to reactive code](https://github.com/home-climate-control/dz/issues/300)
Expand Down
3 changes: 3 additions & 0 deletions docs/release-notes/v4.3.0.md
Original file line number Diff line number Diff line change
Expand Up @@ -3,6 +3,9 @@ Home Climate Control: v4.3.0. Release Notes - DRAFT

Release focus: [Economizer and Scheduler integration](https://github.com/home-climate-control/dz/milestone/18).

## Bugfixes and enhancements
* [#320 Economizer runs forever when there is an ambient sensor failure](https://github.com/home-climate-control/dz/issues/320)

### System Wide Measurement Units Support

Not even quarter of a century later, [Fahrenheit degrees are supported](../configuration/home-climate-control.md#measurement-units).
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -176,7 +176,7 @@ protected final void initFluxes(Flux<Signal<Double, Void>> ambientFlux) {

// Get the signal
var stage2 = computeDeviceState(stage1)
.map(this::recordDeviceState);
.map(this::computeDeviceState);

// And act on it
stage2
Expand Down Expand Up @@ -234,7 +234,13 @@ private void connectCombined(FluxSink<IndoorAmbientPair> sink) {
logger.debug("{}: combined sink ready", getAddress());
}

private Boolean recordDeviceState(Signal<Boolean, ProcessController.Status<Double>> stateSignal) {
/**
* Compute the device state based on the state signal.
*
* @param stateSignal Device state as computed by the pipeline.
* @return State to send to the device.
*/
private Boolean computeDeviceState(Signal<Boolean, ProcessController.Status<Double>> stateSignal) {

var sample = stateSignal.payload == null ? null : ((HysteresisController.HysteresisStatus) stateSignal.payload).sample;
var demand = stateSignal.payload == null ? 0 : stateSignal.payload.signal;
Expand Down Expand Up @@ -317,14 +323,14 @@ private Signal<Double, Void> computeCombined(IndoorAmbientPair pair) {

// No go, incomplete information
logger.debug("{}: null signals? {}", getAddress(), pair);
return new Signal<>(clock.instant(), -1d);
return new Signal<>(clock.instant(), null, null, Signal.Status.FAILURE_TOTAL, new IllegalStateException("null signals, see the log above"));
}

if (pair.indoor.isError() || pair.ambient.isError()) {

// Absolutely not
logger.warn("{}: error signals? {}", getAddress(), pair);
return new Signal<>(clock.instant(), -1d);
return new Signal<>(clock.instant(), null, null, Signal.Status.FAILURE_TOTAL, new IllegalStateException("error signals, see the log above"));
}

// Let's be generous; Zigbee sensors can fall back to 60 seconds interval even if configured faster,
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -9,7 +9,6 @@
import net.sf.dz3r.device.actuator.economizer.EconomizerConfig;
import net.sf.dz3r.model.Thermostat;
import net.sf.dz3r.signal.Signal;
import org.apache.logging.log4j.ThreadContext;
import reactor.core.publisher.Flux;

import java.time.Clock;
Expand All @@ -21,6 +20,8 @@
* More information: <a href="https://github.com/home-climate-control/dz/wiki/HVAC-Device:-Economizer">HVAC Device: Economizer</a>
*
* @param <A> Actuator device address type.
*
* @author Copyright &copy; <a href="mailto:vt@homeclimatecontrol.com">Vadim Tkachenko</a> 2001-2024
*/
public class PidEconomizer<A extends Comparable<A>> extends AbstractEconomizer {

Expand Down Expand Up @@ -73,32 +74,35 @@ public PidEconomizer(
@Override
protected Flux<Signal<Boolean, ProcessController.Status<Double>>> computeDeviceState(Flux<Signal<Double, Void>> pv) {

ThreadContext.push("computeDeviceState");

try {

// Compute the control signal to feed to the renderer.
// Might want to make this available to outside consumers for instrumentation.
var stage1 = controller
.compute(pv)
.doOnNext(e -> logger.debug("controller/{}: {}", getAddress(), e));

// Discard things the renderer doesn't understand.
// Total failure is denoted by NaN by stage 1, it will get through.
// The PID controller output value becomes the extra payload but is ignored at the moment (unlike Thermostat#compute()).
var stage2 = stage1
.map(s -> new Signal<>(s.timestamp, s.getValue().signal, s.getValue(), s.status, s.error));
// Compute the control signal to feed to the renderer.
// Might want to make this available to outside consumers for instrumentation.
var stage1 = controller
.compute(pv)
.doOnNext(e -> logger.debug("controller/{}: {}", getAddress(), e));

// Interpret things the renderer doesn't understand
var stage2 = stage1.map(this::computeRendererInput);

// Deliver the signal
// Might want to expose this as well
return signalRenderer
.compute(stage2)
.doOnNext(e -> logger.debug("renderer/{}: {}", getAddress(), e))
.map(this::mapOutput);
}

// Deliver the signal
// Might want to expose this as well
return signalRenderer
.compute(stage2)
.doOnNext(e -> logger.debug("renderer/{}: {}", getAddress(), e))
.map(this::mapOutput);
/**
* Convert a possibly error signal from the computing pipeline into an actionable signal for the hysteresis controller.
*/
private Signal<Double, ProcessController. Status<Double>> computeRendererInput(Signal<ProcessController.Status<Double>, Void> signal) {

} finally {
ThreadContext.pop();
if (signal.isOK()) {
// PID controller output value becomes the extra payload but is ignored at the moment (unlike Thermostat#compute()).
return new Signal<>(signal.timestamp, signal.getValue().signal, signal.getValue(), signal.status, signal.error);
}

// Any kind of errors at this point must be interpreted as "turn it off"
return new Signal<>(signal.timestamp, -1d);
}

private Signal<Boolean, ProcessController.Status<Double>> mapOutput(Signal<ProcessController.Status<Double>, ProcessController.Status<Double>> source) {
Expand Down
Original file line number Diff line number Diff line change
@@ -0,0 +1,101 @@
package net.sf.dz3r.device.actuator.economizer.v2;

import net.sf.dz3r.device.DeviceState;
import net.sf.dz3r.device.actuator.NullCqrsSwitch;
import net.sf.dz3r.device.actuator.SwitchableHvacDevice;
import net.sf.dz3r.device.actuator.economizer.EconomizerConfig;
import net.sf.dz3r.device.actuator.economizer.EconomizerSettings;
import net.sf.dz3r.model.HvacMode;
import net.sf.dz3r.signal.Signal;
import org.apache.logging.log4j.LogManager;
import org.apache.logging.log4j.Logger;
import org.junit.jupiter.api.Test;
import reactor.core.publisher.Sinks;
import reactor.core.scheduler.Schedulers;

import java.time.Clock;
import java.time.Duration;
import java.util.concurrent.LinkedBlockingQueue;
import java.util.concurrent.TimeoutException;
import java.util.concurrent.atomic.AtomicLong;

import static org.assertj.core.api.Assertions.assertThat;

class PidEconomizerTest {

private final Logger logger = LogManager.getLogger();

/**
* Make sure the economizer stops upon loss of the ambient sensor signal.
*
* See <a href="https://github.com/home-climate-control/dz/issues/320">#320</a>.
*/
@Test
void ambientSensorLoss() throws InterruptedException {

var actuator = new NullCqrsSwitch("test");
var hvac = new SwitchableHvacDevice(
Clock.systemUTC(),
"test",
HvacMode.COOLING,
actuator,
false,
null
);

Sinks.Many<Signal<Double, Void>> ambientSink = Sinks.many().multicast().onBackpressureBuffer();
Sinks.Many<Signal<Double, String>> indoorSink = Sinks.many().multicast().onBackpressureBuffer();

var ambientFlux = ambientSink.asFlux();
var indoorFlux = indoorSink.asFlux();

var eco = new PidEconomizer<>(
Clock.systemUTC(),
"test",
new EconomizerConfig(
HvacMode.COOLING,
1.0,
0.0000008,
1.1,
new EconomizerSettings(
0,
20,
true, 1.0
)

),
ambientFlux,
hvac,
Duration.ofSeconds(10)
);

var output = eco.compute(indoorFlux);
var start = Clock.systemUTC().instant();
var timeStep = 10L;
var offset = new AtomicLong(0);

output
.publishOn(Schedulers.boundedElastic())
.subscribe(step -> logger.info("step: {}", step));

var deviceState = new LinkedBlockingQueue<Signal<DeviceState<Boolean>, String>>();

actuator.getFlux().subscribe(deviceState::add);

// Setup complete, let's push data now

// After receiving just the indoor signal (but not ambient), the economizer is off
indoorSink.tryEmitNext(new Signal<>(start, 25.0, "indoor"));
assertThat(deviceState.take().getValue().requested).isFalse();

// When both indoor and ambient signals are available, it is now on
ambientSink.tryEmitNext(new Signal<>(start.plus(Duration.ofMillis(offset.addAndGet(timeStep))), 20.0));
assertThat(deviceState.take().getValue().requested).isTrue();

// It should turn off now
ambientSink.tryEmitNext(new Signal<>(start.plus(Duration.ofMillis(offset.addAndGet(timeStep))), null, null,Signal.Status.FAILURE_TOTAL, new TimeoutException("oops")));

// ...and it does.
assertThat(deviceState.take().getValue().requested).isFalse();
}
}